Varec, Inc.5834 Peachtree Corners East, Norcross (Atlanta), GA 30092 USATel: +1 (770) 447-9202 Fax: +1 (770) 662-8939www.varec.comIOM019NVAE02084532
Contents Average Temperature/Water Bottom Sensor and Converter4 Installation and Operations Manual
Varec, Inc. 14532 Introduction1 Introduction1.1 IntroductionThe 4532 Average Temperature Sensor and Converter (ATC) is a multi-element (Pt100) resista
Introduction Average Temperature/Water Bottom Sensor and Converter2 Installation and Operations Manual1.4 System functional diagramFigure 1-1: Connec
Varec, Inc. 34532 Safety instructions2 Safety instructions2.1 Installation, commissioning and operation• Mounting, electrical installation, start-up
Safety instructions Average Temperature/Water Bottom Sensor and Converter4 Installation and Operations Manual• Instruments mounted in explosion haza
Varec, Inc. 54532 Safety instructions2.6 Notes on safety conventions and symbolsIn order to highlight safety-relevant or alternative operating procedu
Safety instructions Average Temperature/Water Bottom Sensor and Converter6 Installation and Operations Manual
Varec, Inc. 74532 Identification3 Identification3.1 Device designation3.1.1 NameplateFigure 3-1: 4532 ATC labelsFigure 3-2: Product label for 453x ave
Identification Average Temperature/Water Bottom Sensor and Converter8 Installation and Operations Manual3.3 CE marks, declaration of conformityThe in
Varec, Inc. 94532 Installation4 Installation4.1 Design, dimensionsFigure 4-1: 4532 ATC dimensionsФ10Ф26Bottom hook215 mmFlexible tubedepends on the ta
Installation Average Temperature/Water Bottom Sensor and Converter10 Installation and Operations Manual4.2 UnpackingWhen unpacking, be careful not to
Varec, Inc. 114532 Installation4.4 Installation InstructionsNote! The level sensor circuit is connected to ground and is infallibly galvanically isola
Installation Average Temperature/Water Bottom Sensor and Converter12 Installation and Operations Manual
Varec, Inc. 134532 Mounting5 Mounting5.1 Mounting instructionNote!1. The flexible tube length of the 4532 ATC is defined for the customer’s specifica-
Mounting Average Temperature/Water Bottom Sensor and Converter14 Installation and Operations Manual5.2 Mounting on a fixed roof tankThere are three m
Varec, Inc. 154532 Mounting4. Draw the tensioning wire through the wire hook on the tank bottom.5. Wrap the tensioning wire twice around the hole on t
Mounting Average Temperature/Water Bottom Sensor and Converter16 Installation and Operations Manual5.2.2 Thermo well methodThe flexible tube is inser
Varec, Inc. 174532 Mounting5.2.3 Anchor weight methodThe flexible tube is stabilized by an anchor weight: Figure 5-6: Anchor weight applicationNote! M
Mounting Average Temperature/Water Bottom Sensor and Converter18 Installation and Operations ManualFigure 5-7: Anchor weight mountingFlexible tubePro
Varec, Inc. 194532 Mounting5.3 Mounting on a floating roof tankThere are three methods of mounting the 4532 ATC on a floating roof tank: • Top anchor
Varec, Inc. 14532CopyrightAll rights reserved. Printed in the United States of America. Except as permitted under the United States Copyright Act of 1
Mounting Average Temperature/Water Bottom Sensor and Converter20 Installation and Operations Manual5.3.2 Thermo well methodThe flexible tube is inser
Varec, Inc. 214532 Mounting5.3.3 Guide ring and anchor weight methodThe flexible tube is stabilized by a guide ring and anchor weight.Figure 5-10:Guid
Mounting Average Temperature/Water Bottom Sensor and Converter22 Installation and Operations Manual
Varec, Inc. 234532 Wiring6 Wiring6.1 Terminal Connection6.1.1 4532 ATC terminalNote! The 4532 ATC allows an intrinsically safe HART connection only. P
Wiring Average Temperature/Water Bottom Sensor and Converter24 Installation and Operations Manual6.1.2 6000 Series Servo Tank Gauge terminalSince the
Varec, Inc. 254532 WiringNote! The 4590 TSM has three sets of i.s. HART terminals. These three pairs are looped internally.Caution! Do not connect sig
Wiring Average Temperature/Water Bottom Sensor and Converter26 Installation and Operations Manual
Varec, Inc. 274532 Operating7 Operating7.1 Local HART connection7.1.1 As a Varec tank gauging instrumentThe 4532 ATC has been developed and designated
Operating Average Temperature/Water Bottom Sensor and Converter28 Installation and Operations Manual7.2.2 The 4532 ATC specific parameter set up on t
Varec, Inc. 294532 OperatingGVH447: Reference ZeroIndication of the converted 100 Ohm reference resistor deviation value compared to the actual insert
Average Temperature/Water Bottom Sensor and Converter2 Installation and Operations ManualDisclaimer of WarrantiesThe contract between the Seller and
Operating Average Temperature/Water Bottom Sensor and Converter30 Installation and Operations Manual
Varec, Inc. 314532 Operation and Description of Instrument Function8 Operation and Description of Instrument Function8.0.1 HART Device designationHART
Operation and Description of Instrument Function Average Temperature/Water Bottom Sensor and Converter32 Installation and Operations ManualVH07 Tempe
Varec, Inc. 334532 Operation and Description of Instrument FunctionFormula: (T1 + T2 + T3) / # of element in liquid phase = Average temperature (3.5°C
Operation and Description of Instrument Function Average Temperature/Water Bottom Sensor and Converter34 Installation and Operations Manual(3.5°C x 2
Varec, Inc. 354532 Operation and Description of Instrument FunctionVH29 Upper LimitItem type: read and writeDefault value: 245°CRange: -999.9°C ~ 999.
Operation and Description of Instrument Function Average Temperature/Water Bottom Sensor and Converter36 Installation and Operations ManualVH48 Gas O
Varec, Inc. 374532 Operation and Description of Instrument Function8.1.6 WB primary and Advanced temp: VH50 ~ VH59VH53 Element PointItem type: selectD
Operation and Description of Instrument Function Average Temperature/Water Bottom Sensor and Converter38 Installation and Operations ManualVH69 Ref V
Varec, Inc. 394532 Operation and Description of Instrument FunctionVH73: "Temperature X" = raw element temperature x span (VH72) + zero offs
Varec, Inc. 34532Safety Precaution DefinitionsCaution! Damage to equipment may result if this precaution is disregarded.Warning! Direct injury to pers
Operation and Description of Instrument Function Average Temperature/Water Bottom Sensor and Converter40 Installation and Operations ManualVH79 Prote
Varec, Inc. 414532 Operation and Description of Instrument FunctionVH80: Present ErrorItem type: read onlyDisplay of current error message. One of the
Operation and Description of Instrument Function Average Temperature/Water Bottom Sensor and Converter42 Installation and Operations ManualVH82 Eleme
Varec, Inc. 434532 Operation and Description of Instrument FunctionVH87 Element IntervalItem type: read and writeDefault: 1000mm Range: 0mm ~ 99999mmA
Operation and Description of Instrument Function Average Temperature/Water Bottom Sensor and Converter44 Installation and Operations ManualVH92 Error
Varec, Inc. 454532 Maintenance9 MaintenanceThe 4532 ATC Average temperature instrument requires no special maintenance.9.1 Exterior cleaningWhen clean
Maintenance Average Temperature/Water Bottom Sensor and Converter46 Installation and Operations Manual9.4 ReplacementAfter a complete 4532 ATC electr
Varec, Inc. 474532 Troubleshooting10 Troubleshooting10.1 System error messagesThese error codes are displayed on the ToF tool display when the ToF too
Troubleshooting Average Temperature/Water Bottom Sensor and Converter48 Installation and Operations Manual10.2 Spare partsSpare parts are contained i
Varec, Inc. 494532 Accessories11 Accessories11.1 Anchor weight (Tall profile)Caution! Installation of anchor weight will cause element position #1 (th
Average Temperature/Water Bottom Sensor and Converter4 Installation and Operations Manual
Accessories Average Temperature/Water Bottom Sensor and Converter50 Installation and Operations Manual11.3 Wire hook, Top anchorAnchor weights are su
Varec, Inc. 514532 Technical data12 Technical dataTechnical data at a glance:ApplicationApplication The 4532 ATC performs precise liquid and gas phase
Technical data Average Temperature/Water Bottom Sensor and Converter52 Installation and Operations Manual
Varec, Inc. 534532 Order StructureA Order Structure10 Protection class7 FM, IS class1, Div.1, Gr. A-DB ATEX, EEx [ia] IIB T4 -T620 Cable entryB Thread
Order Structure Average Temperature/Water Bottom Sensor and Converter54 Installation and Operations Manual
Varec, Inc. 554532 Declaration of Contamination FormB Declaration of Contamination FormVarec, Inc., an SAIC Company5834 Peachtree Corners East, Norcro
Declaration of Contamination Form Average Temperature/Water Bottom Sensor and Converter56 Installation and Operations Manual
Varec, Inc. 574532 IndexIndexDDesignated use 1Eexplosion-proof type 3GGrounding 4HHazardous Substance Datasheet 4Iinstallation & operation ove
Index Average Temperature/Water Bottom Sensor and Converter58 Installation and Operations Manual
Varec, Inc. 594532NOTES
Varec, Inc. 14532 ContentsContents1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.1
Your offical representativeVarec, Inc.5834 Peachtree Corners East, Norcross (Atlanta), GA 30092 USATel: +1 (770) 447-9202 Fax: +1 (770) 662-8939© Var
Contents Average Temperature/Water Bottom Sensor and Converter2 Installation and Operations Manual5.2.3 Anchor weight method . . . . . . . . . . . .
Varec, Inc. 34532 Contents10 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4710.1 System error
Komentarze do niniejszej Instrukcji